Re: CAN bus -- Interview question
raj katoch <[email protected]>
| Newsgroups | gmane.comp.hardware.bus.can |
|---|---|
| Message-ID | <CAB2555GbJTU6W9CgMv6Ov4OGaR6MqjihfCCGq0GAtk1SXtU+9A@mail.gmail.com> |
Thanks for your reply John & Rufus. regards, katoch On Thu, Oct 11, 2012 at 11:04 PM, Rufus V. Smith <[email protected]>wrote: > Just one case where complete power removal isn't the best: > > If you have a conveyor controlled by servomotors, you can decelerate it > quicker with the > servo controller active, rather than by removing power (and letting it > coast to a stop). > > If something has to *STOP!* , you probably need external emergency braking > in the system, that > functions when ESTOP removes power (as it should). > > (P.S. The fact that my car brake pedals aren't directly tied to brake > shoes still bothers me....) > > Rufus > > > > > Rufus V. Smith Faria Watchdog [email protected] On 10/11/2012 > 12:07 PM, John Dammeyer wrote: > > Not sure I understand your question. The Link you provided clearly states > the reason for the pull cord along a conveyor belt. Since it's an ESTOP > the CAN bus has nothing to do with it other than perhaps reporting via a > second switch inside the box that the ESTOP was activated. > > What to do with the ESTOP comes up often in the home hobby or small > business CNC groups all the time. There's a big red button on the PC user > screen marked stop and it's attached via a port pin to a physical button or > some other sort of switch. Once active this big red soft button starts > flashing the CNC software will no longer issues stepping pulses or provide > control outputs. > > But it's not an ESTOP even though it looks like one. Intrinsically safe > systems remove power to all life threatening equipment when pressed. So AC > power vanishes since the AC is dangerous. The AC also moves the conveyor > belt and with it removed the belt stops. Motors stop. That operator being > electrocuted by a frayed wire no longer is frozen by the current to the > wire and drops away. > > There are arguments that if the power is removed that then the machine > cannot be manually operated to help remove someone pinned by the machine. > This is true. But that is an after the event activity to be dealt with by > emergency response people. They may well restart the system in a manual > override mode that lets them then reverse motors slowly etc. > > But an ESTOP should initially remove all power. Lately though I believe > PCs and user interfaces are being exempted by that rule and only power to > motion gear is physically removed. > > Let the counter arguments begin. <GRIN> > > John Dammeyer > > > > *"ELS! The Solution" > *Automation Artisans Inc. > http://www.autoartisans.com/ELS/ > Ph. 1 250 544 4950 > > -----Original Message----- > *From:* [email protected] [ > mailto:[email protected]<[email protected]>] > *On Behalf Of *raj katoch > *Sent:* Thursday, October 11, 2012 3:46 AM > *To:* Canlist > *Subject:* [CANLIST] CAN bus -- Interview question > > Hi, > > There were few question which i was not able to answer in an interview > today. > One of them i will like to ask on list :--- > > What is the use of this Pull cord switches on Conveyor belt ? > What role CAN bus plays it may be the field bus to transfer event to stop > the belt power supply, is it right ? > > http://www.martin-eng.com/resources/blog/emergency-stop-switches > > > thanks & regards, > > katoch > > >