Re: Server failover

Aaron Ball <[email protected]>
Newsgroups gmane.comp.time.chrony.user
Message-ID <CAETEtSMGvx-wSDRbjpo43aWtimGrTL7WoaGBW8bNqkK3epb8qQ@mail.gmail.com>
On Fri, Aug 12, 2022 at 11:11 AM Kevin P. Fleming <kevin-vUBz/[email protected]> wrote:

> > We use redundant time servers in each of our datacenters, and we'd like
> to actively switch away from time servers before their scheduled reboots,
> because the estimated error that accumulates on our clients while waiting
> to notice that a server has gone away can be too high for our standards.
>
> Are the clients connecting to all of the redundant servers? If so,
> losing connectivity to one shouldn't have much impact since the others
> will still be working.
>

Clients are always connected to two servers in the same/nearest available
datacenter, and to several backup servers elsewhere. We use "trust" and
"prefer" flags on the near two. When one goes away, clients take about 10
minutes to switch. For regulatory reasons, we care about 100us deviations,
which is < 0.2 ppm over 10 minutes.