RE: Received Trap Won't Decode

[email protected]
Newsgroups gmane.network.net-snmp.user
Message-ID <20090609205817.292eb6c930850de810cf35869bff7bc4.38997ebe3d.wbe@email.secureserver.net>
I installed the UPS-MIB, see attached.  Set "mibs +UPS-MIB" in
/etc/snmp/snmp.conf and restarted the snmptrapd and snmpd servers.


When I look at the sent trap via wireshark ( data below),
is the trap .1.3.5.1.2.1.33.4.6.4?


I know the trap I have a definition for is .1.3.5.1.2.1.33.2.0.2 from
using snmptranslate...

me@en:/$ snmptranslate -m +UPS-MIB -IR -Of upsTrapTestCompleted
.iso.org.dod.internet.mgmt.mib-2.upsMIB.upsTraps.upsTraps#.upsTrapTestCompleted
me@en:/$ snmptranslate -m +UPS-MIB -IR -On upsTrapTestCompleted
.1.3.6.1.2.1.33.2.0.2


Wireshark trap packet decode:
Simple Network Management Protocol
.version: version-1 (0)
.community: myUPS
.data: trap (4)
..trap
...enterprise: 1.3.6.1.2.1.33 (RFC1213-MIB::mib-2.33)
...agent-addr: 0.1.0.0 (0.1.0.0)
...generic-trap: enterpriseSpecific (6)
...specific-trap: 4
...time-stamp: 82014
...variable-bindings: 0 items 



>> Am I to assume the MIB is broken?
>
>No - it loaded OK for me.
>But the MIB you posted doesn't cover the traps that you
>are receiving. Those traps are rooted at mib-2.33,
>while the UPSD-MIB is rooted at enterprises.2254
>
>I think you actually need the UPS-MIB (RFC 1628)
>
>Dave

------------------------------------------------------------------------------
Crystal Reports - New Free Runtime and 30 Day Trial
Check out the new simplified licensing option that enables unlimited
royalty-free distribution of the report engine for externally facing 
server and web deployment.
http://p.sf.net/sfu/businessobjects

_______________________________________________
Net-snmp-users mailing list
[email protected]
Please see the following page to unsubscribe or change other options:
https://lists.sourceforge.net/lists/listinfo/net-snmp-users
UPS-MIB.txt (text/x-java, 47.8 KB)
-- automatically generated by mosy 7.1 #379 (dbc), do not edit!
-- UPS-MIB, defined for SNMP version 1
-- 5/22/94

-- Defines Internet Standard UPS MIB (from RFC-1628)
-- Traps defined with normal variables listed (no interface variables)
-- Work-arounds for plain old SNMP version 1:
--                                      Tom Brennan, Exide Electronics, 9/7/94

-- Further sanitized for SNMP version 1 and comments restored from RFC1628
--                                      Tom Brennan, Exide Electronics, 3/30/95

-- Corrected upper Integer range from 2147483648 to 2147483647
-- Changed import from mib-2, which some NMSs couldn't do, to mgmt
--                                      Tom Brennan, Exide Electronics, 11/27/96

-- restore "upsMIB MODULE-IDENTITY" from RFC1628
--                                                 Arnaud Quette, EATON, 2/27/09


UPS-MIB DEFINITIONS ::= BEGIN

IMPORTS
--      AutonomousType
--              FROM RFC1316-MIB
--      Use ObjectID instead of this SNMP version 2 type
        TRAP-TYPE
                FROM RFC-1215
        DisplayString
                FROM RFC1213-MIB
        OBJECT-TYPE
                FROM RFC-1212
        mgmt, Gauge, Counter, TimeTicks
                FROM RFC1155-SMI;
--      TestAndIncr, TimeInterval, TimeStamp
--              FROM SNMPv2-TC;
--      Use Integer, TimeTicks, and TimeTicks instead of these SNMP v2 types

-- created from upsMIB (9402230000Z)

mib-2  OBJECT IDENTIFIER ::= { mgmt 1 }

upsMIB MODULE-IDENTITY
    LAST-UPDATED "9402230000Z"
    ORGANIZATION "IETF UPS MIB Working Group"
    CONTACT-INFO
           "        Jeffrey D. Case

             Postal: SNMP Research, Incorporated
                     3001 Kimberlin Heights Road
                     Knoxville, TN  37920
                     US

                Tel: +1 615 573 1434
                Fax: +1 615 573 9197

             E-mail: [email protected]"
    DESCRIPTION
            "The MIB module to describe Uninterruptible Power
            Supplies."
    ::= { mib-2 33 }

-- upsMIB OBJECT IDENTIFIER ::= { mib-2  33 }

-- Replaced references to PositiveInteger and NonNegativeInteger
-- Corrected upper Integer range from 2147483648 to 2147483647


upsObjects OBJECT IDENTIFIER ::= { upsMIB  1 }

--
-- The Device Identification group.
--      All objects in this group except for upsIdentName and
--      upsIdentAttachedDevices are set at device initialization
--      and remain static.
--

upsIdent OBJECT IDENTIFIER ::= { upsObjects  1 }

upsIdentManufacturer OBJECT-TYPE
    SYNTAX  DisplayString (SIZE (0..31))
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The name of the UPS manufacturer."
    ::= { upsIdent  1 }

upsIdentModel OBJECT-TYPE
    SYNTAX  DisplayString (SIZE (0..63))
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS Model designation."
    ::= { upsIdent  2 }

upsIdentUPSSoftwareVersion OBJECT-TYPE
    SYNTAX  DisplayString (SIZE (0..63))
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS firmware/software version(s).  This variable
               may or may not have the same value as
               upsIdentAgentSoftwareVersion in some implementations."
    ::= { upsIdent  3 }

upsIdentAgentSoftwareVersion OBJECT-TYPE
    SYNTAX  DisplayString (SIZE (0..63))
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The UPS agent software version.  This variable may or
               may not have the same value as
               upsIdentUPSSoftwareVersion in some implementations."
    ::= { upsIdent  4 }

upsIdentName OBJECT-TYPE
    SYNTAX  DisplayString (SIZE (0..63))
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "A string identifying the UPS.  This object should be
               set by the administrator."
    ::= { upsIdent  5 }

upsIdentAttachedDevices OBJECT-TYPE
    SYNTAX  DisplayString (SIZE (0..63))
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "A string identifying the devices attached to the
               output(s) of the UPS.  This object should be set by
               the administrator."
    ::= { upsIdent  6 }


--
-- Battery Group
--

upsBattery OBJECT IDENTIFIER ::= { upsObjects  2 }

upsBatteryStatus OBJECT-TYPE
    SYNTAX  INTEGER {
    unknown(1),
    batteryNormal(2),
    batteryLow(3),
    batteryDepleted(4)
}
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The indication of the capacity remaining in the UPS
               system's batteries.   A value of batteryNormal
               indicates that the remaining run-time is greater than
               upsConfigLowBattTime.  A value of batteryLow indicates
               that the remaining battery run-time is less than or
               equal to upsConfigLowBattTime.  A value of
               batteryDepleted indicates that the UPS will be unable
               to sustain the present load when and if the utility
               power is lost (including the possibility that the
               utility power is currently absent and the UPS is
               unable to sustain the output)."
    ::= { upsBattery  1 }

upsSecondsOnBattery OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS seconds
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "If the unit is on battery power, the elapsed time
               since the UPS last switched to battery power, or the
               time since the network management subsystem was last
               restarted, whichever is less.  Zero shall be returned
               if the unit is not on battery power."
    ::= { upsBattery  2 }

upsEstimatedMinutesRemaining OBJECT-TYPE
    SYNTAX  INTEGER (1..2147483647)     -- UNITS minutes
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "An estimate of the time to battery charge depletion
               under the present load conditions if the utility power
               is off and remains off, or if it were to be lost and
               remain off."
    ::= { upsBattery  3 }

upsEstimatedChargeRemaining OBJECT-TYPE
    SYNTAX  INTEGER (0..100)    -- UNITS percent
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "An estimate of the battery charge remaining expressed
               as a percent of full charge."
    ::= { upsBattery  4 }

upsBatteryVoltage OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS 0.1 Volt DC
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The magnitude of the present battery voltage."
    ::= { upsBattery  5 }

upsBatteryCurrent OBJECT-TYPE
    SYNTAX  INTEGER (-2147483648..2147483647)   -- UNITS 0.1 Amp DC
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present battery current."
    ::= { upsBattery  6 }

upsBatteryTemperature OBJECT-TYPE
    SYNTAX  INTEGER (-2147483648..2147483647)   -- UNITS degrees Centigrade
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The ambient temperature at or near the UPS Battery
               casing."
    ::= { upsBattery  7 }


--
-- Input Group
--

upsInput OBJECT IDENTIFIER ::= { upsObjects  3 }

upsInputLineBads OBJECT-TYPE
    SYNTAX  Counter
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "A count of the number of times the input entered an
               out-of-tolerance condition as defined by the
               manufacturer.  This count is incremented by one each
               time the input transitions from zero out-of-tolerance
               lines to one or more input lines out-of-tolerance."
    ::= { upsInput  1 }

upsInputNumLines OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The number of input lines utilized in this device.
               This variable indicates the number of rows in the
               input table."
    ::= { upsInput  2 }

upsInputTable OBJECT-TYPE
    SYNTAX  SEQUENCE OF UpsInputEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "A list of input table entries.  The number of entries
               is given by the value of upsInputNumLines."
    ::= { upsInput  3 }

upsInputEntry OBJECT-TYPE
    SYNTAX  UpsInputEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "An entry containing information applicable to a
               particular input line."
    INDEX   { upsInputLineIndex }
    ::= { upsInputTable  1 }

UpsInputEntry ::=
    SEQUENCE {
        upsInputLineIndex
            INTEGER,

        upsInputFrequency
            INTEGER,

        upsInputVoltage
            INTEGER,

        upsInputCurrent
            INTEGER,

        upsInputTruePower
            INTEGER
    }

upsInputLineIndex OBJECT-TYPE
    SYNTAX  INTEGER (1..2147483647)
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "The input line identifier."
    ::= { upsInputEntry  1 }

upsInputFrequency OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS 0.1 Hertz
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present input frequency."
    ::= { upsInputEntry  2 }

upsInputVoltage OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS RMS Volts
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The magnitude of the present input voltage."
    ::= { upsInputEntry  3 }

upsInputCurrent OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS 0.1 RMS Amp
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The magnitude of the present input current."
    ::= { upsInputEntry  4 }

upsInputTruePower OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS Watts
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The magnitude of the present input true power."
    ::= { upsInputEntry  5 }


--
-- The Output group.
--

upsOutput OBJECT IDENTIFIER ::= { upsObjects  4 }

upsOutputSource OBJECT-TYPE
    SYNTAX  INTEGER {
    other(1),
    none(2),
    normal(3),
    bypass(4),
    battery(5),
    booster(6),
    reducer(7)
}
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present source of output power.  The enumeration
               none(2) indicates that there is no source of output
               power (and therefore no output power), for example,
               the system has opened the output breaker."
    ::= { upsOutput  1 }

upsOutputFrequency OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS 0.1 Hertz
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present output frequency."
    ::= { upsOutput  2 }

upsOutputNumLines OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The number of output lines utilized in this device.
               This variable indicates the number of rows in the
               output table."
    ::= { upsOutput  3 }

upsOutputTable OBJECT-TYPE
    SYNTAX  SEQUENCE OF UpsOutputEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "A list of output table entries.  The number of
               entries is given by the value of upsOutputNumLines."
    ::= { upsOutput  4 }

upsOutputEntry OBJECT-TYPE
    SYNTAX  UpsOutputEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "An entry containing information applicable to a
               particular output line."
    INDEX   { upsOutputLineIndex }
    ::= { upsOutputTable  1 }

UpsOutputEntry ::=
    SEQUENCE {
        upsOutputLineIndex
            INTEGER,

        upsOutputVoltage
            INTEGER,

        upsOutputCurrent
            INTEGER,

        upsOutputPower
            INTEGER,

        upsOutputPercentLoad
            INTEGER
    }

upsOutputLineIndex OBJECT-TYPE
    SYNTAX  INTEGER (1..2147483647)
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "The output line identifier."
    ::= { upsOutputEntry  1 }

upsOutputVoltage OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS RMS Volts
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present output voltage."
    ::= { upsOutputEntry  2 }

upsOutputCurrent OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS 0.1 RMS Amp
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present output current."
    ::= { upsOutputEntry  3 }

upsOutputPower OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS Watts
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present output true power."
    ::= { upsOutputEntry  4 }

upsOutputPercentLoad OBJECT-TYPE
    SYNTAX  INTEGER (0..200) -- UNITS percent
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The percentage of the UPS power capacity presently
               being used on this output line, i.e., the greater of
               the percent load of true power capacity and the
               percent load of VA."
    ::= { upsOutputEntry  5 }


--
-- The Bypass group.
--

upsBypass OBJECT IDENTIFIER ::= { upsObjects  5 }

upsBypassFrequency OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS 0.1 Hertz
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present bypass frequency."
    ::= { upsBypass  1 }

upsBypassNumLines OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The number of bypass lines utilized in this device.
               This entry indicates the number of rows in the bypass
               table."
    ::= { upsBypass  2 }

upsBypassTable OBJECT-TYPE
    SYNTAX  SEQUENCE OF UpsBypassEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "A list of bypass table entries.  The number of
               entries is given by the value of upsBypassNumLines."
    ::= { upsBypass  3 }

upsBypassEntry OBJECT-TYPE
    SYNTAX  UpsBypassEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "An entry containing information applicable to a
               particular bypass input."
    INDEX   { upsBypassLineIndex }
    ::= { upsBypassTable  1 }

UpsBypassEntry ::=
    SEQUENCE {
        upsBypassLineIndex
            INTEGER,

        upsBypassVoltage
            INTEGER,

        upsBypassCurrent
            INTEGER,

        upsBypassPower
            INTEGER
    }

upsBypassLineIndex OBJECT-TYPE
    SYNTAX  INTEGER (1..2147483647)
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "The bypass line identifier."
    ::= { upsBypassEntry  1 }

upsBypassVoltage OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS RMS Volts
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present bypass voltage."
    ::= { upsBypassEntry  2 }

upsBypassCurrent OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS 0.1 RMS Amp

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present bypass current."
    ::= { upsBypassEntry  3 }

upsBypassPower OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS Watts

    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present true power conveyed by the bypass."
    ::= { upsBypassEntry  4 }


--
-- The Alarm group.
--

upsAlarm OBJECT IDENTIFIER ::= { upsObjects  6 }

upsAlarmsPresent OBJECT-TYPE
    SYNTAX  Gauge
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The present number of active alarm conditions."
    ::= { upsAlarm  1 }

upsAlarmTable OBJECT-TYPE
    SYNTAX  SEQUENCE OF UpsAlarmEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "A list of alarm table entries.  The table contains
               zero, one, or many rows at any moment, depending upon
               the number of alarm conditions in effect.  The table
               is initially empty at agent startup.  The agent
               creates a row in the table each time a condition is
               detected and deletes that row when that condition no
               longer pertains.  The agent creates the first row with
               upsAlarmId equal to 1, and increments the value of
               upsAlarmId each time a new row is created, wrapping to
               the first free value greater than or equal to 1 when
               the maximum value of upsAlarmId would otherwise be
               exceeded.  Consequently, after multiple operations,
               the table may become sparse, e.g., containing entries
               for rows 95, 100, 101, and 203 and the entries should
               not be assumed to be in chronological order because
               upsAlarmId might have wrapped.

               Alarms are named by an AutonomousType (OBJECT
               IDENTIFIER), upsAlarmDescr, to allow a single table to
               reflect well known alarms plus alarms defined by a
               particular implementation, i.e., as documented in the
               private enterprise MIB definition for the device.  No
               two rows will have the same value of upsAlarmDescr,
               since alarms define conditions.  In order to meet this
               requirement, care should be taken in the definition of
               alarm conditions to insure that a system cannot enter
               the same condition multiple times simultaneously.

               The number of rows in the table at any given time is
               reflected by the value of upsAlarmsPresent."
    ::= { upsAlarm  2 }

upsAlarmEntry OBJECT-TYPE
    SYNTAX  UpsAlarmEntry
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "An entry containing information applicable to a





               particular alarm."
    INDEX   { upsAlarmId }
    ::= { upsAlarmTable  1 }

UpsAlarmEntry ::=
    SEQUENCE {
        upsAlarmId
            INTEGER,

        upsAlarmDescr
            OBJECT IDENTIFIER,

        upsAlarmTime
            TimeTicks
    }

upsAlarmId OBJECT-TYPE
    SYNTAX  INTEGER (1..2147483647)
    ACCESS  not-accessible
    STATUS  mandatory
    DESCRIPTION
           "A unique identifier for an alarm condition.  This
               value must remain constant."
    ::= { upsAlarmEntry  1 }

upsAlarmDescr OBJECT-TYPE
--  SYNTAX  AutonomousType
    SYNTAX  OBJECT IDENTIFIER
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "A reference to an alarm description object.  The
               object referenced should not be accessible, but rather
               be used to provide a unique description of the alarm
               condition."
    ::= { upsAlarmEntry  2 }

upsAlarmTime OBJECT-TYPE
--  SYNTAX  TimeStamp
    SYNTAX  TimeTicks
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The value of sysUpTime when the alarm condition was
               detected.  If the alarm condition was detected at the
               time of agent startup and presumably existed before
               agent startup, the value of upsAlarmTime shall equal
               0."
    ::= { upsAlarmEntry  3 }


--
-- Well known alarm conditions.
--

upsWellKnownAlarms OBJECT IDENTIFIER ::= { upsAlarm  3 }

upsAlarmBatteryBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms  1 }
--      "One or more batteries have been determined to require replacement."

upsAlarmOnBattery OBJECT IDENTIFIER ::= { upsWellKnownAlarms  2 }
--      "The UPS is drawing power from the batteries."

upsAlarmLowBattery OBJECT IDENTIFIER ::= { upsWellKnownAlarms  3 }
--      "The remaining battery run-time is less than or equal
--      to upsConfigLowBattTime."

upsAlarmDepletedBattery OBJECT IDENTIFIER ::= { upsWellKnownAlarms  4 }
--      "The UPS will be unable to sustain the present load
--      when and if the utility power is lost."

upsAlarmTempBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms  5 }
--      "A temperature is out of tolerance."

upsAlarmInputBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms  6 }
--      "An input condition is out of tolerance."

upsAlarmOutputBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms  7 }
--      "An output condition (other than OutputOverload) is
--      out of tolerance."

upsAlarmOutputOverload OBJECT IDENTIFIER ::= { upsWellKnownAlarms  8 }
--      "The output load exceeds the UPS output capacity."

upsAlarmOnBypass OBJECT IDENTIFIER ::= { upsWellKnownAlarms  9 }
--      "The Bypass is presently engaged on the UPS."

upsAlarmBypassBad OBJECT IDENTIFIER ::= { upsWellKnownAlarms  10 }
--      "The Bypass is out of tolerance."

upsAlarmOutputOffAsRequested OBJECT IDENTIFIER ::= { upsWellKnownAlarms  11 }
--      "The UPS has shutdown as requested, i.e., the output is off."

upsAlarmUpsOffAsRequested OBJECT IDENTIFIER ::= { upsWellKnownAlarms  12 }
--      "The entire UPS has shutdown as commanded."

upsAlarmChargerFailed OBJECT IDENTIFIER ::= { upsWellKnownAlarms  13 }
--      "An uncorrected problem has been detected within the
--      UPS charger subsystem."

upsAlarmUpsOutputOff OBJECT IDENTIFIER ::= { upsWellKnownAlarms  14 }
--      "The output of the UPS is in the off state."

upsAlarmUpsSystemOff OBJECT IDENTIFIER ::= { upsWellKnownAlarms  15 }
--      "The UPS system is in the off state."

upsAlarmFanFailure OBJECT IDENTIFIER ::= { upsWellKnownAlarms  16 }
--      "The failure of one or more fans in the UPS has been detected."

upsAlarmFuseFailure OBJECT IDENTIFIER ::= { upsWellKnownAlarms  17 }
--      "The failure of one or more fuses has been detected."

upsAlarmGeneralFault OBJECT IDENTIFIER ::= { upsWellKnownAlarms  18 }
--      "A general fault in the UPS has been detected."

upsAlarmDiagnosticTestFailed OBJECT IDENTIFIER ::= { upsWellKnownAlarms  19 }
--      "The result of the last diagnostic test indicates a failure."

upsAlarmCommunicationsLost OBJECT IDENTIFIER ::= { upsWellKnownAlarms  20 }
--      "A problem has been encountered in the communications
--      between the agent and the UPS."

upsAlarmAwaitingPower OBJECT IDENTIFIER ::= { upsWellKnownAlarms  21 }
--      "The UPS output is off and the UPS is awaiting the
--      return of input power."

upsAlarmShutdownPending OBJECT IDENTIFIER ::= { upsWellKnownAlarms  22 }
--      "A upsShutdownAfterDelay countdown is underway."

upsAlarmShutdownImminent OBJECT IDENTIFIER ::= { upsWellKnownAlarms  23 }
--      "The UPS will turn off power to the load in less than
--      5 seconds; this may be either a timed shutdown or a
--      low battery shutdown."

upsAlarmTestInProgress OBJECT IDENTIFIER ::= { upsWellKnownAlarms  24 }
--      "A test is in progress, as initiated and indicated by
--      the Test Group."


--
-- The Test Group
--

upsTest OBJECT IDENTIFIER ::= { upsObjects  7 }

upsTestId OBJECT-TYPE
    SYNTAX  OBJECT IDENTIFIER
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "The test is named by an OBJECT IDENTIFIER which
               allows a standard mechanism for the initiation of
               tests, including the well known tests identified in
               this document as well as those introduced by a
               particular implementation, i.e., as documented in the
               private enterprise MIB definition for the device.

               Setting this variable initiates the named test. Sets
               to this variable require the presence of
               upsTestSpinLock in the same SNMP message.

               The set request will be rejected with an appropriate
               error message if the requested test cannot be
               performed, including attempts to start a test when
               another test is already in progress.  The status of
               the current or last test is maintained in
               upsTestResultsSummary. Tests in progress may be
               aborted by setting the upsTestId variable to
               upsTestAbortTestInProgress.

               Read operations return the value of the name of the
               test in progress if a test is in progress or the name
               of the last test performed if no test is in progress,
               unless no test has been run, in which case the well
               known value upsTestNoTestsInitiated is returned."
    ::= { upsTest  1 }

upsTestSpinLock OBJECT-TYPE
--  SYNTAX  TestAndIncr
    SYNTAX  INTEGER (0..2147483647)
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "A spin lock on the test subsystem.  The spinlock is
               used as follows.

               Before starting a test, a manager-station should make
               sure that a test is not in progress as follows:

               try_again:
                 get (upsTestSpinLock)
                 while (upsTestResultsSummary == inProgress) {
                   /* loop while a test is running for another manager */
                   short delay
                   get (upsTestSpinLock)
                 }
                 lock_value = upsTestSpinLock
                 /* no test in progress, start the test */
                 set (upsTestSpinLock = lock_value, upsTestId = requested_test)
                 if (error_index == 1) { /* (upsTestSpinLock failed) */
                   /* if problem is not access control, then
                      some other manager slipped in ahead of us */
                   goto try_again
                 }
                 if (error_index == 2) { /* (upsTestId) */
                   /* cannot perform the test */
                   give up
                 }
                 /* test started ok */
                 /* wait for test completion by polling upsTestResultsSummary */
                 get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail)
                 while (upsTestResultsSummary == inProgress) {
                   short delay
                   get (upsTestSpinLock, upsTestResultsSummary, upsTestResultsDetail)
                 }
                 /* when test completes, retrieve any additional test results;
                    if upsTestSpinLock == lock_value + 1, then these are our
                    test results (as opposed to another manager's */
             The initial value of upsTestSpinLock at agent initialization
                shall be 1."
    ::= { upsTest  2 }

upsTestResultsSummary OBJECT-TYPE
    SYNTAX  INTEGER {
    donePass(1),
    doneWarning(2),
    doneError(3),
    aborted(4),
    inProgress(5),
    noTestsInitiated(6)
}
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The results of the current or last UPS diagnostics
               test performed.  The values for donePass(1),
               doneWarning(2), and doneError(3) indicate that the
               test completed either successfully, with a warning, or
               with an error, respectively.  The value aborted(4) is
               returned for tests which are aborted by setting the
               value of upsTestId to upsTestAbortTestInProgress.
               Tests which have not yet concluded are indicated by
               inProgress(5).  The value noTestsInitiated(6)
               indicates that no previous test results are available,
               such as is the case when no tests have been run since
               the last reinitialization of the network management
               subsystem and the system has no provision for non-
               volatile storage of test results."
    ::= { upsTest  3 }

upsTestResultsDetail OBJECT-TYPE
    SYNTAX  DisplayString  (SIZE (0..255))
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "Additional information about upsTestResultsSummary.
               If no additional information available, a zero length
               string is returned."
    ::= { upsTest  4 }

upsTestStartTime OBJECT-TYPE
--  SYNTAX  TimeStamp
    SYNTAX  TimeTicks
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The value of sysUpTime at the time the test in
               progress was initiated, or, if no test is in progress,
               the time the previous test was initiated.  If the
               value of upsTestResultsSummary is noTestsInitiated(6),
               upsTestStartTime has the value 0."
    ::= { upsTest  5 }

upsTestElapsedTime OBJECT-TYPE
--  SYNTAX  TimeInterval
    SYNTAX  TimeTicks
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The amount of time, in TimeTicks, since the test in
               progress was initiated, or, if no test is in progress,
               the previous test took to complete.  If the value of
               upsTestResultsSummary is noTestsInitiated(6),
               upsTestElapsedTime has the value 0."
    ::= { upsTest  6 }

--
-- Well known tests.
--

upsWellKnownTests OBJECT IDENTIFIER ::= { upsTest  7 }

upsTestNoTestsInitiated OBJECT IDENTIFIER ::= { upsWellKnownTests  1 }
--      "No tests have been initiated and no test is in progress."

upsTestAbortTestInProgress OBJECT IDENTIFIER ::= { upsWellKnownTests  2 }
--      "The test in progress is to be aborted / the test in
--      progress was aborted."

upsTestGeneralSystemsTest OBJECT IDENTIFIER ::= { upsWellKnownTests  3 }
--      "The manufacturer's standard test of UPS device systems."

upsTestQuickBatteryTest OBJECT IDENTIFIER ::= { upsWellKnownTests  4 }
--      "A test that is sufficient to determine if the battery
--      needs replacement."

upsTestDeepBatteryCalibration OBJECT IDENTIFIER ::= { upsWellKnownTests  5 }
--      "The system is placed on battery to a discharge level,
--      set by the manufacturer, sufficient to determine
--      battery replacement and battery run-time with a high
--      degree of confidence.  WARNING:  (see RFC 1628.TXT)"


--
-- The Control group.
--

upsControl OBJECT IDENTIFIER ::= { upsObjects  8 }

upsShutdownType OBJECT-TYPE
    SYNTAX  INTEGER {
    output(1),
    system(2)
}
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "This object determines the nature of the action to be
               taken at the time when the countdown of the
               upsShutdownAfterDelay and upsRebootWithDuration
               objects reaches zero.

               Setting this object to output(1) indicates that
               shutdown requests should cause only the output of the
               UPS to turn off.  Setting this object to system(2)
               indicates that shutdown requests will cause the entire
               UPS system to turn off."
    ::= { upsControl  1 }

upsShutdownAfterDelay OBJECT-TYPE
    SYNTAX  INTEGER (-1..2147483647)    -- UNITS seconds
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "Setting this object will shutdown (i.e., turn off)
               either the UPS output or the UPS system (as determined
               by the value of upsShutdownType at the time of
               shutdown) after the indicated number of seconds, or
               less if the UPS batteries become depleted. Setting
               this object to 0 will cause the shutdown to occur
               immediately.  Setting this object to -1 will abort the
               countdown.  If the system is already in the desired
               state at the time the countdown reaches 0, then
               nothing will happen.  That is, there is no additional
               action at that time if upsShutdownType = system and
               the system is already off.  Similarly, there is no
               additional action at that time if upsShutdownType =
               output and the output is already off.  When read,
               upsShutdownAfterDelay will return the number of
               seconds remaining until shutdown, or -1 if no shutdown
               countdown is in effect.  On some systems, if the agent
               is restarted while a shutdown countdown is in effect,
               the countdown may be aborted.  Sets to this object
               override any upsShutdownAfterDelay already in effect."
    ::= { upsControl  2 }

upsStartupAfterDelay OBJECT-TYPE
    SYNTAX  INTEGER (-1..2147483647)     -- UNITS seconds
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "Setting this object will start the output after the
               indicated number of seconds, including starting the
               UPS, if necessary.  Setting this object to 0 will
               cause the startup to occur immediately.  Setting this
               object to -1 will abort the countdown.  If the output
               is already on at the time the countdown reaches 0,
               then nothing will happen.  Sets to this object
               override the effect of any upsStartupAfterDelay
               countdown or upsRebootWithDuration countdown in
               progress.  When read, upsStartupAfterDelay will return
               the number of seconds until startup, or -1 if no
               startup countdown is in effect.  If the countdown
               expires during a utility failure, the startup shall
               not occur until the utility power is restored.  On
               some systems, if the agent is restarted while a
               startup countdown is in effect, the countdown is
               aborted."
    ::= { upsControl  3 }

upsRebootWithDuration OBJECT-TYPE
    SYNTAX  INTEGER (-1..300)    -- UNITS seconds
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "Setting this object will immediately shutdown (i.e.,
               turn off) either the UPS output or the UPS system (as
               determined by the value of upsShutdownType at the time
               of shutdown) for a period equal to the indicated
               number of seconds, after which time the output will be
               started, including starting the UPS, if necessary.  If
               the number of seconds required to perform the request
               is greater than the requested duration, then the
               requested shutdown and startup cycle shall be
               performed in the minimum time possible, but in no case
               shall this require more than the requested duration
               plus 60 seconds.  When read, upsRebootWithDuration
               shall return the number of seconds remaining in the
               countdown, or -1 if no countdown is in progress.  If
               the startup should occur during a utility failure, the
               startup shall not occur until the utility power is
               restored."
    ::= { upsControl  4 }

upsAutoRestart OBJECT-TYPE
    SYNTAX  INTEGER {
    on(1),
    off(2)
}
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "Setting this object to 'on' will cause the UPS system
               to restart after a shutdown if the shutdown occurred
               during a power loss as a result of either a
               upsShutdownAfterDelay or an internal battery depleted
               condition.  Setting this object to 'off' will prevent
               the UPS system from restarting after a shutdown until
               an operator manually or remotely explicitly restarts
               it.  If the UPS is in a startup or reboot countdown,
               then the UPS will not restart until that delay has
               been satisfied."
    ::= { upsControl  5 }


--
-- The Configuration group.
--

upsConfig OBJECT IDENTIFIER ::= { upsObjects  9 }

upsConfigInputVoltage OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS RMS Volts
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "The magnitude of the nominal input voltage.  On those
               systems which support read-write access to this
               object, if there is an attempt to set this variable to
               a value that is not supported, the request must be
               rejected and the agent shall respond with an
               appropriate error message, i.e., badValue for SNMPv1,
               or inconsistentValue for SNMPv2."
    ::= { upsConfig  1 }

upsConfigInputFreq OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS 0.1 Hertz
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "The nominal input frequency.  On those systems which
               support read-write access to this object, if there is
               an attempt to set this variable to a value that is not
               supported, the request must be rejected and the agent
               shall respond with an appropriate error message, i.e.,
               badValue for SNMPv1, or inconsistentValue for SNMPv2."
    ::= { upsConfig  2 }

upsConfigOutputVoltage OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS RMS Volts
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "The magnitude of the nominal output voltage.  On
               those systems which support read-write access to this
               object, if there is an attempt to set this variable to
               a value that is not supported, the request must be
               rejected and the agent shall respond with an
               appropriate error message, i.e., badValue for SNMPv1,
               or inconsistentValue for SNMPv2."
    ::= { upsConfig  3 }

upsConfigOutputFreq OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS 0.1 Hertz
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "The nominal output frequency.  On those systems which
               support read-write access to this object, if there is
               an attempt to set this variable to a value that is not
               supported, the request must be rejected and the agent
               shall respond with an appropriate error message, i.e.,
               badValue for SNMPv1, or inconsistentValue for SNMPv2."
    ::= { upsConfig  4 }

upsConfigOutputVA OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS Volt-Amps
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The magnitude of the nominal Volt-Amp rating."
    ::= { upsConfig  5 }

upsConfigOutputPower OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS Watts
    ACCESS  read-only
    STATUS  mandatory
    DESCRIPTION
           "The magnitude of the nominal true power rating."
    ::= { upsConfig  6 }

upsConfigLowBattTime OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS minutes
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "The value of upsEstimatedMinutesRemaining at which a
               lowBattery condition is declared.  For agents which
               support only discrete (discontinuous) values, then the
               agent shall round up to the next supported value.  If
               the requested value is larger than the largest
               supported value, then the largest supported value
               shall be selected."
    ::= { upsConfig  7 }

upsConfigAudibleStatus OBJECT-TYPE
    SYNTAX  INTEGER {
    disabled(1),
    enabled(2),
    muted(3)
}
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "The requested state of the audible alarm.  When in
               the disabled state, the audible alarm should never
               sound.  The enabled state is self-describing.  Setting
               this object to muted(3) when the audible alarm is
               sounding shall temporarily silence the alarm.  It will
               remain muted until it would normally stop sounding and
               the value returned for read operations during this
               period shall equal muted(3).  At the end of this
               period, the value shall revert to enabled(2).  Writes
               of the value muted(3) when the audible alarm is not
               sounding shall be accepted but otherwise shall have no
               effect."
    ::= { upsConfig  8 }

upsConfigLowVoltageTransferPoint OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS RMS Volts
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "The minimum input line voltage allowed before the UPS
               system transfers to battery backup."
    ::= { upsConfig  9 }

upsConfigHighVoltageTransferPoint OBJECT-TYPE
    SYNTAX  INTEGER (0..2147483647)  -- UNITS RMS Volts
    ACCESS  read-write
    STATUS  mandatory
    DESCRIPTION
           "The maximum line voltage allowed before the UPS
               system transfers to battery backup."
    ::= { upsConfig  10 }


--
-- notifications, i.e., traps
--

upsTraps OBJECT IDENTIFIER ::= { upsMIB  2 }

-- This section defines the well-known notifications sent by
-- UPS agents.

upsTrapOnBattery TRAP-TYPE
    ENTERPRISE  upsTraps
    VARIABLES   { upsEstimatedMinutesRemaining,  upsSecondsOnBattery,
upsConfigLowBattTime }
    DESCRIPTION
           "The UPS is operating on battery power.  This trap is
               persistent and is resent at one minute intervals until
               the UPS either turns off or is no longer running on
               battery."
    ::= 1

upsTrapTestCompleted TRAP-TYPE
    ENTERPRISE  upsTraps
    VARIABLES   { upsTestId,  upsTestSpinLock,  upsTestResultsSummary,
upsTestResultsDetail,  upsTestStartTime,  upsTestElapsedTime }
    DESCRIPTION
           "This trap is sent upon completion of a UPS diagnostic
               test."
    ::= 2

upsTrapAlarmEntryAdded TRAP-TYPE
    ENTERPRISE  upsTraps
    VARIABLES   { upsAlarmId,  upsAlarmDescr }
    DESCRIPTION
           "This trap is sent each time an alarm is inserted into
               to the alarm table.  It is sent on the insertion of
               all alarms except for upsAlarmOnBattery and
               upsAlarmTestInProgress."
    ::= 3

upsTrapAlarmEntryRemoved TRAP-TYPE
    ENTERPRISE  upsTraps
    VARIABLES   { upsAlarmId,  upsAlarmDescr }
    DESCRIPTION
           "This trap is sent each time an alarm is removed from
               the alarm table.  It is sent on the removal of all
               alarms except for upsAlarmTestInProgress."
    ::= 4


--
-- conformance information and compliance statements
-- Note: the following definitions are not useful for SNMP v1, but
--       are given here to represent the complete MIB from RFC1628
--

upsConformance OBJECT IDENTIFIER ::= { upsMIB  3 }

upsCompliances OBJECT IDENTIFIER ::= { upsConformance  1 }

upsSubsetCompliance OBJECT IDENTIFIER ::= { upsCompliances  1 }

upsBasicCompliance OBJECT IDENTIFIER ::= { upsCompliances  2 }

upsFullCompliance OBJECT IDENTIFIER ::= { upsCompliances  3 }


--
-- units of conformance
--

-- summary at a glance:

--                                      subset  basic   advanced
--upsIdentManufacturer                  x       x       x
--upsIdentModel                         x       x       x
--upsIdentUPSSoftwareVersion                    x       x
--upsIdentAgentSoftwareVersion          x       x       x
--upsIdentName                          x       x       x
--upsIdentAttachedDevices               x               x
--
--upsBatteryStatus                      x       x       x  notes
--upsSecondsOnBattery                   x       x       x
--upsEstimatedMinutesRemaining                          x
--upsEstimatedChargeRemaining                           x
--upsBatteryVoltage
--upsBatteryCurrent
--upsBatteryTemperature
--
--upsInputLineBads                      x       x       x
--upsInputNumLines                              x       x
--upsInputFrequency                             x       x
--upsInputVoltage                               x       x
--upsInputCurrent
--upsInputTruePower
--
--upsOutputSource                       x       x       x  notes
--upsOutputFrequency                            x       x
--upsOutputNumLines                             x       x
--upsOutputVoltage                              x       x
--upsOutputCurrent                                      x
--upsOutputPower                                        x
--upsOutputPercentLoad                                  x
--
--
--upsBypassFrequency                            x       x  notes
--upsBypassNumLines                             x       x
--upsBypassVoltage                              x       x
--upsBypassCurrent
--upsBypassPower
--
--
--upsAlarmsPresent                      x       x       x
--upsAlarmDescr                         x       x       x  notes
--upsAlarmTime                          x       x       x
--
--upsTestId                                     x       x  notes
--upsTestSpinLock                               x       x
--upsTestResultsSummary                         x       x
--upsTestResultsDetail                          x       x
--upsTestStartTime                              x       x
--upsTestElapsedTime                            x       x
--
--upsShutdownType                       x       x       x  notes
--upsShutdownAfterDelay                 x       x       x
--upsStartupAfterDelay                          x       x
--upsRebootWithDuration                         x       x
--upsAutoRestart                        x       x       x  notes
--
--upsConfigInputVoltage                 x       x       x  notes
--upsConfigInputFreq                    x       x       x  notes
--upsConfigOutputVoltage                x       x       x  notes
--upsConfigOutputFreq                   x       x       x  notes
--upsConfigOutputVA                     x       x       x
--upsConfigOutputPower                  x       x       x
--upsConfigLowBattTime                          x       x  notes
--upsConfigAudibleStatus                        x       x
--upsConfigLowVoltageTransferPoint
--upsConfigHighVoltageTransferPoint



upsGroups OBJECT IDENTIFIER ::= { upsConformance  2 }

upsSubsetGroups OBJECT IDENTIFIER ::= { upsGroups  1 }

upsSubsetIdentGroup OBJECT IDENTIFIER ::= { upsSubsetGroups  1 }

upsSubsetBatteryGroup OBJECT IDENTIFIER ::= { upsSubsetGroups  2 }

upsSubsetInputGroup OBJECT IDENTIFIER ::= { upsSubsetGroups  3 }

upsSubsetOutputGroup OBJECT IDENTIFIER ::= { upsSubsetGroups  4 }

upsSubsetAlarmGroup OBJECT IDENTIFIER ::= { upsSubsetGroups  6 }

upsSubsetControlGroup OBJECT IDENTIFIER ::= { upsSubsetGroups  8 }

upsSubsetConfigGroup OBJECT IDENTIFIER ::= { upsSubsetGroups  9 }

upsBasicGroups OBJECT IDENTIFIER ::= { upsGroups  2 }

upsBasicIdentGroup OBJECT IDENTIFIER ::= { upsBasicGroups  1 }

upsBasicBatteryGroup OBJECT IDENTIFIER ::= { upsBasicGroups  2 }

upsBasicInputGroup OBJECT IDENTIFIER ::= { upsBasicGroups  3 }

upsBasicOutputGroup OBJECT IDENTIFIER ::= { upsBasicGroups  4 }

upsBasicBypassGroup OBJECT IDENTIFIER ::= { upsBasicGroups  5 }

upsBasicAlarmGroup OBJECT IDENTIFIER ::= { upsBasicGroups  6 }

upsBasicTestGroup OBJECT IDENTIFIER ::= { upsBasicGroups  7 }

upsBasicControlGroup OBJECT IDENTIFIER ::= { upsBasicGroups  8 }

upsBasicConfigGroup OBJECT IDENTIFIER ::= { upsBasicGroups  9 }

upsFullGroups OBJECT IDENTIFIER ::= { upsGroups  3 }

upsFullIdentGroup OBJECT IDENTIFIER ::= { upsFullGroups  1 }

upsFullBatteryGroup OBJECT IDENTIFIER ::= { upsFullGroups  2 }

upsFullInputGroup OBJECT IDENTIFIER ::= { upsFullGroups  3 }

upsFullOutputGroup OBJECT IDENTIFIER ::= { upsFullGroups  4 }

upsFullBypassGroup OBJECT IDENTIFIER ::= { upsFullGroups  5 }

upsFullAlarmGroup OBJECT IDENTIFIER ::= { upsFullGroups  6 }

upsFullTestGroup OBJECT IDENTIFIER ::= { upsFullGroups  7 }

upsFullControlGroup OBJECT IDENTIFIER ::= { upsFullGroups  8 }

upsFullConfigGroup OBJECT IDENTIFIER ::= { upsFullGroups  9 }

END