Re: [MISC] Coupure électrique PA3 ?!

Michaël BLANDIN via frnog <[email protected]>
Newsgroups gmane.org.operators.frnog
Message-ID <CAHe56ubcPONUtfjhXFVxF2PkZtgwBmZA1zRQUxn2fZOavFAUDQ@mail.gmail.com>
Pas d'impact visible pour nous en DH5. Dernier mail en date



*IBX:* PA3
*IBX Address:* 114 Rue Ambroise Croizat, Saint Denis, 93200
*Number: *INC0192098
*Date and Time of Occurrence:* 07-APR-2026 08:42:09 Site Local Time

To view the incident and its updates, please use Service Insight.

New update on Incident INC0192098:
Incident Summary
Equinix IBX Site Staff reports that a power disturbance was detected at the
PA3 IBX involving the Uninterruptible Power Supply (UPS). A warning alarm
was observed while customer loads continued to be supported by utility
power. The event has stabilized and site electrical conditions are
currently normal.

Service Impact
There was no customer impact, and no customer cabinets were affected. No
risk to customer services was identified. Operational redundancy and
cabinet redundancy remain normal.

Suspected Root Cause
The suspected root cause of the event is a power dip. Further analysis did
not identify any additional abnormalities at this time.

Mitigation & Planned Actions
IBX Critical Facilities Engineer advised that vendor engagement was not
required. IBX Site Staff are continuing to monitor the system to ensure
electrical stability. The next update will be provided once monitoring has
concluded or if any significant changes occur in the situation.

   - *Customer Impact: *Non-Service Impacting
   - *Service Offering:* PA3 - Electrical - UPSS
   - *Affected Assets:* PA3-UPS-7.3, PA3-UPS-4.4, PA3-MSS-3, PA3-UPS-5.4,
   PA3-MSS-4, PA3-UPS-4.2, PA3-UPS-5.1, PA3-MSS-5, PA3-UPS-5.3, PA3-UPS-5.2,
   ...
   (Please find the full list on Service Insight
   - *Asset Condition:* Normal and Monitoring
   - *Current system redundancy:* Reduced Redundancy
   - *Suspected Initial Cause: *Power dip
   - *Situation status: *Stable
   - *Resources on site/pending:* N/A
   - *Generator fuel run time (hrs):* 120
   - *Current colo humidity RH status:* Humidity stable, within SLA
   - *Current colo temperature status:* Temperature stable, within SLA


Le mar. 7 avr. 2026 à 10:32, Nicolas GIRARDI via frnog <[email protected]> a
écrit :

> Bonjour,
>
> Depuis 8h22 je suis en incident. A priori une coupure électrique sur
> toutes les chaînes d’après mon hébergeur.
>
> Avez vous des infos ?
> Merci.
>
> Nicolas Girardi.
>
> ---------------------------