RE: slightly off topic

"Blake Pfankuch" <bpfankuch-iDUpQSA8o47qlBn2x/[email protected]>
Newsgroups gmane.org.operators.internet-access
Message-ID <[email protected]>
The load wasn't dropped on the utility side.  I checked it with a multi
meter.  And we do have a generator there, and it is right before the
fuses I was speaking of.  And it didn't kick in because it didn't detect
bad voltage.  What I am specifically asking is if anyone else has seen a
fuse similar to this, or if they can justify reasoning for these being
on this circuit.

-----Original Message-----
From: [email protected] [mailto:[email protected]]
On Behalf Of John van Oppen (list account)
Sent: Sunday, March 02, 2008 10:30 AM
To: [email protected]
Subject: RE: slightly off topic

One of the phases could have been dropped on the utility side as well.
However, if you have a generator with a good transfer switch it should
detect that and transfer your whole load to backup power.



-----Original Message-----
From: [email protected] [mailto:[email protected]]
On Behalf Of Blake Pfankuch
Sent: Sunday, March 02, 2008 7:16 AM
To: [email protected]
Subject: RE: slightly off topic

That's exactly what happened but not in the way we would have expected.
We went to the main to that room, popped it open and got the handy multi
meter.  Hot side tested at 208.  Other side at 104.  We figured we had
lost 1 fuse.  So we swapped out one of the fuses.  Multi meter showed
160 ish.  The fuse we just pulled out, check the resistance on it and it
was fine.  Removed the other fuse on the main and put the one we just
pulled out in, and it was 208 like it should be.  Now the weirdest part,
the last fuse we pulled out tested good as well.  Anyone ever run into
something like this?

-----Original Message-----
From: [email protected] [mailto:[email protected]]
On Behalf Of joe mcguckin
Sent: Sunday, March 02, 2008 2:47 AM
To: [email protected]
Subject: Re: slightly off topic

It sounds like you lost one phase of your  power.  low voltage phase  
to neutral loads (for devices
connected to the still live phase) would be unaffected, but higher  
voltage phase-to-phase devices would stop working.

Joe McGuckin
ViaNet Communications

[email protected]
650-207-0372 cell
650-213-1302 office
650-969-2124 fax



On Mar 1, 2008, at 8:55 PM, Blake Pfankuch wrote:

> So we ran into an issue the other night that was power related, long
> story short the mains to the datacenter had the wrong fuses.  Anyone
> ever run into Slow Blow Voltage limiting fuses?  When they actually
> trigger, the limit voltage passing through them to 50% until you reset
> them by removing them and putting them back in.  These were 100A fuses
> on a 220 main.  The way the room was wired, it allowed some stuff to
> still function as it was 110, but the rest of the 220 stuff died out.
> Can anyone think of a practical reason to put these on dedicated mains
> to a small datacenter?
>
> Thanks
>
> Blake Pfankuch
> _______________________________________________
> "Eat sushi frequently". - Avi
> [email protected] is the human contact address.
> [email protected] is the list posting address.
> See below URL for subscribe/unsubscribe and list options:
> http://inet-access.net/mailman/listinfo/list

_______________________________________________
"Eat sushi frequently". - Avi
[email protected] is the human contact address.
[email protected] is the list posting address.
See below URL for subscribe/unsubscribe and list options:
http://inet-access.net/mailman/listinfo/list
_______________________________________________
"Eat sushi frequently". - Avi
[email protected] is the human contact address.
[email protected] is the list posting address.
See below URL for subscribe/unsubscribe and list options:
http://inet-access.net/mailman/listinfo/list
_______________________________________________
"Eat sushi frequently". - Avi
[email protected] is the human contact address.
[email protected] is the list posting address.
See below URL for subscribe/unsubscribe and list options:
http://inet-access.net/mailman/listinfo/list
_______________________________________________
"Eat sushi frequently". - Avi
[email protected] is the human contact address.
[email protected] is the list posting address.
See below URL for subscribe/unsubscribe and list options:
http://inet-access.net/mailman/listinfo/list
lmpx.com only provides a reader for public news (NNTP) servers. It is not affiliated with the servers or forums shown here and is not responsible for the content of articles, which is written by their respective authors.