Re: Data Colo Facilities in Northern NJ
Drew Linsalata <[email protected]>
| Newsgroups | gmane.org.operators.internet-access |
|---|---|
| Message-ID | <[email protected]> |
Design max on any given circuit is usually 80%. Beyond that, all bets are usually off as it seems you've discovered. :-) Drew Linsalata The Gotham Bus Company, Inc. Colocation and Dedicated Server Solutions http://www.gothambus.com On Mar 3, 2008, at 4:54 PM, Jeff Koch wrote: > > In our experience it's really impossible to actually use a constant > 20 amps. We'll load in servers till we're up to around 16-17 amps - > any higher and a spike of high activity could force the amps over > the limit and trip the circuit breakers. The actual amps used by > our servers will tend to vary - power usage seems to go up in the > middle of the night when we do our backups. > _______________________________________________ "Eat sushi frequently". - Avi [email protected] is the human contact address. [email protected] is the list posting address. See below URL for subscribe/unsubscribe and list options: http://inet-access.net/mailman/listinfo/list