Re: slightly off topic

Mark Radabaugh <[email protected]>
Newsgroups gmane.org.operators.internet-access
Message-ID <[email protected]>
Blake Pfankuch wrote:
> They do, that's how we came to the conclusion they were slow blow
> voltage regulating 100 amp fuses.
>
>   
Hum... In many many years of industrial power and controls work I can't 
say I have ever seen such a beast.  

Slow Blow Current Limiting fuses are extremely common.   Due to the 
extremely low inductance of the electrical distribution system fault 
currents can be very large and damaging.  Current Limiting fuses are 
designed to limit the fault currents to 200,000 or 300,000 amps and to 
open in less then 1/4 cycle.   In low impedance circuits it is common to 
have both a breaker and a fuse.   Breakers are simply unable to 
effectively interrupt the fault currents caused by catastrophic 
faults.   Current limiting fuses work by vaporizing the material inside 
the fuse which creates enough pressure to stop the arc.

What is the manufacturer's marking on the fuse?   The part number alone 
should be enough to find the manufacturers data sheet.

I have seen plenty of truly odd voltage readings on 3 phase circuits 
when a single leg of a 3 phase circuit is open.   Depending on the 
configuration (delta/wye) and where the ground is the readings can be 
all over the map.   Very high impedance digital meters (very common 
these days) can also give odd voltage readings on open circuits.   The 
voltage and current on the surrounding conductors can induce hundreds of 
volts onto an open wire (though it has very little current available) 
and the meter will show voltage.  Check the same wire with an older 
analog meter or wiggy 
(http://www.us.schneider-electric.com/us/products/machine_safety.nsf/unid/58870E11543C976885256D500050927B/$file/wiggy.htm) 
and you won't find anything.

Mark
_______________________________________________
"Eat sushi frequently". - Avi
[email protected] is the human contact address.
[email protected] is the list posting address.
See below URL for subscribe/unsubscribe and list options:
http://inet-access.net/mailman/listinfo/list
lmpx.com only provides a reader for public news (NNTP) servers. It is not affiliated with the servers or forums shown here and is not responsible for the content of articles, which is written by their respective authors.