Jeff Koch wrote:
> 
> In our experience it's really impossible to actually use a constant 20 
> amps. We'll load in servers till we're up to around 16-17 amps - any 
> higher and a spike of high activity could force the amps over the limit 
> and trip the circuit breakers. The actual amps used by our servers will 
> tend to vary -  power usage seems to go up in the middle of the night 
> when we do our backups.

As they say at Burger King, "Have it your way".

But do also re-run the math using the power pricing as $0.20.  You're 
now talking $276 to power your 16A draw and $276 to cool your 16A draw. 
  A $500 cabinet now represents a $52 monthly loss before the real 
estate, staff, capital, etc. costs are ever considered.