slightly off topic
"Blake Pfankuch" <bpfankuch-iDUpQSA8o47qlBn2x/[email protected]>
| Newsgroups | gmane.org.operators.internet-access |
|---|---|
| Message-ID | <[email protected]> |
So we ran into an issue the other night that was power related, long story short the mains to the datacenter had the wrong fuses. Anyone ever run into Slow Blow Voltage limiting fuses? When they actually trigger, the limit voltage passing through them to 50% until you reset them by removing them and putting them back in. These were 100A fuses on a 220 main. The way the room was wired, it allowed some stuff to still function as it was 110, but the rest of the 220 stuff died out. Can anyone think of a practical reason to put these on dedicated mains to a small datacenter? Thanks Blake Pfankuch _______________________________________________ "Eat sushi frequently". - Avi [email protected] is the human contact address. [email protected] is the list posting address. See below URL for subscribe/unsubscribe and list options: http://inet-access.net/mailman/listinfo/list