Re: slightly off topic
joe mcguckin <[email protected]>
| Newsgroups | gmane.org.operators.internet-access |
|---|---|
| Message-ID | <[email protected]> |
It sounds like you lost one phase of your power. low voltage phase to neutral loads (for devices connected to the still live phase) would be unaffected, but higher voltage phase-to-phase devices would stop working. Joe McGuckin ViaNet Communications [email protected] 650-207-0372 cell 650-213-1302 office 650-969-2124 fax On Mar 1, 2008, at 8:55 PM, Blake Pfankuch wrote: > So we ran into an issue the other night that was power related, long > story short the mains to the datacenter had the wrong fuses. Anyone > ever run into Slow Blow Voltage limiting fuses? When they actually > trigger, the limit voltage passing through them to 50% until you reset > them by removing them and putting them back in. These were 100A fuses > on a 220 main. The way the room was wired, it allowed some stuff to > still function as it was 110, but the rest of the 220 stuff died out. > Can anyone think of a practical reason to put these on dedicated mains > to a small datacenter? > > Thanks > > Blake Pfankuch > _______________________________________________ > "Eat sushi frequently". - Avi > [email protected] is the human contact address. > [email protected] is the list posting address. > See below URL for subscribe/unsubscribe and list options: > http://inet-access.net/mailman/listinfo/list _______________________________________________ "Eat sushi frequently". - Avi [email protected] is the human contact address. [email protected] is the list posting address. See below URL for subscribe/unsubscribe and list options: http://inet-access.net/mailman/listinfo/list