IT sounds to me more like a bad connection at the mains or in your
panel.  You may want to have your electrition disassemble and clean the
connections, using a high quality anti-corrosive grease.  I have seen
problems very similar form dirty/loose mains connections.  Look for hot
bits in your panel or other wiring.  If anything is dropping half the
voltage for a NOC ohms law demands that it will get very warm.  

 

> -----Original Message-----
> From: [email protected] 
> [mailto:[email protected]] On Behalf Of John van 
> Oppen (list account)
> Sent: Sunday, March 02, 2008 11:30 AM
> To: [email protected]
> Subject: RE: slightly off topic
> 
> One of the phases could have been dropped on the utility side as well.
> However, if you have a generator with a good transfer switch 
> it should detect that and transfer your whole load to backup power.
> 
> 
> 
> -----Original Message-----
> From: [email protected] 
> [mailto:[email protected]]
> On Behalf Of Blake Pfankuch
> Sent: Sunday, March 02, 2008 7:16 AM
> To: [email protected]
> Subject: RE: slightly off topic
> 
> That's exactly what happened but not in the way we would have 
> expected.
> We went to the main to that room, popped it open and got the 
> handy multi meter.  Hot side tested at 208.  Other side at 
> 104.  We figured we had lost 1 fuse.  So we swapped out one 
> of the fuses.  Multi meter showed 160 ish.  The fuse we just 
> pulled out, check the resistance on it and it was fine.  
> Removed the other fuse on the main and put the one we just 
> pulled out in, and it was 208 like it should be.  Now the 
> weirdest part, the last fuse we pulled out tested good as 
> well.  Anyone ever run into something like this?
> 
> -----Original Message-----
> From: [email protected] 
> [mailto:[email protected]]
> On Behalf Of joe mcguckin
> Sent: Sunday, March 02, 2008 2:47 AM
> To: [email protected]
> Subject: Re: slightly off topic
> 
> It sounds like you lost one phase of your  power.  low 
> voltage phase to neutral loads (for devices connected to the 
> still live phase) would be unaffected, but higher voltage 
> phase-to-phase devices would stop working.
> 
> Joe McGuckin
> ViaNet Communications
> 
> [email protected]
> 650-207-0372 cell
> 650-213-1302 office
> 650-969-2124 fax
> 
> 
> 
> On Mar 1, 2008, at 8:55 PM, Blake Pfankuch wrote:
> 
> > So we ran into an issue the other night that was power 
> related, long 
> > story short the mains to the datacenter had the wrong 
> fuses.  Anyone 
> > ever run into Slow Blow Voltage limiting fuses?  When they actually 
> > trigger, the limit voltage passing through them to 50% 
> until you reset 
> > them by removing them and putting them back in.  These were 
> 100A fuses 
> > on a 220 main.  The way the room was wired, it allowed some 
> stuff to 
> > still function as it was 110, but the rest of the 220 stuff 
> died out.
> > Can anyone think of a practical reason to put these on 
> dedicated mains 
> > to a small datacenter?
> >
> > Thanks
> >
> > Blake Pfankuch
> > _______________________________________________
> > "Eat sushi frequently". - Avi
> > [email protected] is the human contact address.
> > [email protected] is the list posting address.
> > See below URL for subscribe/unsubscribe and list options:
> > http://inet-access.net/mailman/listinfo/list
> 
> _______________________________________________
> "Eat sushi frequently". - Avi
> [email protected] is the human contact address.
> [email protected] is the list posting address.
> See below URL for subscribe/unsubscribe and list options:
> http://inet-access.net/mailman/listinfo/list
> _______________________________________________
> "Eat sushi frequently". - Avi
> [email protected] is the human contact address.
> [email protected] is the list posting address.
> See below URL for subscribe/unsubscribe and list options:
> http://inet-access.net/mailman/listinfo/list
> _______________________________________________
> "Eat sushi frequently". - Avi
> [email protected] is the human contact address.
> [email protected] is the list posting address.
> See below URL for subscribe/unsubscribe and list options:
> http://inet-access.net/mailman/listinfo/list
> 
_______________________________________________
"Eat sushi frequently". - Avi
[email protected] is the human contact address.
[email protected] is the list posting address.
See below URL for subscribe/unsubscribe and list options:
http://inet-access.net/mailman/listinfo/list
lmpx.com only provides a reader for public news (NNTP) servers. It is not affiliated with the servers or forums shown here and is not responsible for the content of articles, which is written by their respective authors.