Re: Data Colo Facilities in Northern NJ

jp <[email protected]>
Newsgroups gmane.org.operators.internet-access
Message-ID <[email protected]>
If you are using 15amp receptacles with a 20amp breaker at your house, 
you have a bad electrician. (except unless that receptacle is dedicated 
to a motorized load that trips a 15a breaker)

If you run a 20amp circuit at close to 20amps, you will warm the wiring, 
warm the breaker, and that warming is wasted electricity that would have 
paid for beefier wiring in a relatively short time. It's not a bad thing 
to warm wiring within it's design limits, but it's a costly waste of 
electricity for continuous loads.

If a colo customer runs something at close to 20amps, and trips the 
20amp breaker, they do not have access to the power distribution system 
and they will be out of service till they can rouse me and wait for me 
to arrive to flip the breaker and provide them some advice. 

On Mon, Mar 03, 2008 at 04:01:53PM -0600, Kevin Kargel wrote:
> 80% power is really the target.  While a 20A breaker trips at 20A, if
> you try to run it at 20A continuous it will overheat and fail
> prematurely.  If you need an honest 20A consumption you will need to get
> a 30A circuit.  Did you ever notice that the breakers in your house are
> 20A but your outlets are only rated at 15A?  This is why.  
> 
> > -----Original Message-----
> > From: [email protected] 
> > [mailto:[email protected]] On Behalf Of Jeff Koch
> > Sent: Monday, March 03, 2008 3:54 PM
> > To: [email protected]
> > Subject: Re: Data Colo Facilities in Northern NJ
> > 
> > 
> > In our experience it's really impossible to actually use a 
> > constant 20 amps. We'll load in servers till we're up to 
> > around 16-17 amps - any higher and a spike of high activity 
> > could force the amps over the limit and trip the circuit 
> > breakers. The actual amps used by our servers will tend to vary
> > -  power usage seems to go up in the middle of the night when 
> > we do our backups.
> > 
> > 
> > 
> > At 03:34 PM 3/3/2008, you wrote:
> > >Jeff Koch wrote:
> > >>
> > >>Thanks to all that responded. We're getting some good leads. Our 
> > >>current cost for a cabinet with one 20AMP power connection seems to 
> > >>have gone from $500/month to almost $900/month during the last two 
> > >>years. Does that seem reasonable? or are we getting hosed?
> > >
> > >120V/20A translates to 2400w or 2.4kw.  24 hours/day * 30 
> > days/month = 
> > >720 hours.  2.4kw for 720 hours = 1728 kwhr.  At $0.07 per kwhr, the 
> > >raw utility cost to feed your cabinet would be $121, but I'd 
> > guess that 
> > >$0.07 could be quite conservative.
> > >
> > >Many sites find that their infrastructure (cooling, etc.) 
> > takes another 
> > >60-150% to operate.  At a reasonable average of 100% 
> > operational costs, 
> > >you're looking at another $121 to cool your cabinet.  Throw in some 
> > >amortization of gensets, PDUs, etc., and related systems, 
> > and it starts 
> > >to make sense.
> > >
> > >Given the trend of increasing power densities, gone are the 
> > days where 
> > >that 20A feed per cabinet was running at 2-5A and a shop 
> > could throw in 
> > >the power for free.
> > >
> > >pt
> > >_______________________________________________
> > >"Eat sushi frequently". - Avi
> > >[email protected] is the human contact address.
> > >[email protected] is the list posting address.
> > >See below URL for subscribe/unsubscribe and list options:
> > >http://inet-access.net/mailman/listinfo/list
> > 
> > Best Regards,
> > 
> > Jeff Koch, Intersessions 
> > 
> > _______________________________________________
> > "Eat sushi frequently". - Avi
> > [email protected] is the human contact address.
> > [email protected] is the list posting address.
> > See below URL for subscribe/unsubscribe and list options:
> > http://inet-access.net/mailman/listinfo/list
> > 
> _______________________________________________
> "Eat sushi frequently". - Avi
> [email protected] is the human contact address.
> [email protected] is the list posting address.
> See below URL for subscribe/unsubscribe and list options:
> http://inet-access.net/mailman/listinfo/list

-- 
/*
Jason Philbrook   |   Midcoast Internet Solutions - Wireless and DSL
    KB1IOJ        |   Broadband Internet Access, Dialup, and Hosting 
 http://f64.nu/   |   for Midcoast Maine    http://www.midcoast.com/
*/
-- 
Eat sushi frequently. - Avi
[email protected] is the human contact address.
[email protected] is the list posting address.
See below URL for subscribe/unsubscribe and list options:
http://inet-access.net/mailman/listinfo/list
lmpx.com only provides a reader for public news (NNTP) servers. It is not affiliated with the servers or forums shown here and is not responsible for the content of articles, which is written by their respective authors.