Re: Data Colo Facilities in Northern NJ
Pete Templin <[email protected]>
| Newsgroups | gmane.org.operators.internet-access |
|---|---|
| Message-ID | <[email protected]> |
Alex Rubenstein wrote: >> But do also re-run the math using the power pricing as $0.20. You're >> now talking $276 to power your 16A draw and $276 to cool your 16A draw. >> A $500 cabinet now represents a $52 monthly loss before the real >> estate, staff, capital, etc. costs are ever considered. > > If this is true, you have a bad HVAC contractor. > > Typically, in the industry, for every 100 watts into the building, 57 should > go to critical load, and 43 to "other". As was quoted to me in two different forums, (total power draw / "IT" power draw) is typically 1.6 to 2.5. You're saying it's 1.75. I chose a middle-of-the-road estimate, 2, since the math was easier. At 1.75, you're talking $208 to manage (and yes, I'm changing terminology from "cool") that $276 draw. $484 in direct costs leaves little margin on a $500 cabinet to pay for real estate, batteries, security, cabinets, etc. And it's not necessarily the HVAC contractor. If there's condensation dripping or flowing out of the CRAC, something's not tuned right, and it might not be the contractor. pt -- Eat sushi frequently. - Avi [email protected] is the human contact address. [email protected] is the list posting address. See below URL for subscribe/unsubscribe and list options: http://inet-access.net/mailman/listinfo/list