Re: 120V in 208 environment

Jay Hennigan <[email protected]>
Newsgroups gmane.org.operators.internet-access
Message-ID <[email protected]>
James Jun wrote:
> Hello,
> 
>  
> 
> Does anyone have any recommendations on best practices for following 
> scenario:
> 
>  
> 
> I have a rack with 3-phase 208V power and will be delivering power to 
> the servers inside the rack in 208V, using per-outlet-metering PDU.  The 
> issue is that I need to supply at least one 120V port for maintenance 
> uses (i.e. plug in KVM cart, etc) and I can’t justify spending another 
> $200/mo to drop in a 120V circuit for that purpose.
> 
>  
> 
> ServerTech apparently makes Switched CDU’s that provide 208V power 
> in/out (3-phase Wye input) and have one Utility Port at the bottom 
> running in 120V as NEMA 5-20R, which solves my dilemma.  But the problem 
> is that they do not offer this on their POPS (pwer-outlet-power-sensing) 
> products yet, and I need the per-outlet monitoring capability.
> 
>  
> 
> Does anyone know of any PDU vendors that can provide power monitoring 
> down to every outlet while offering both 208 and 120volts output?  Or 
> failing that, does anyone know of any decent 1U rackmountable step-down 
> transformers that can take 208V input in an IEC connector and output 
> 120V in standard NEMA 5-15R or 5-20R connectors?
> 
>  
> 
> It seems I have a very strange power requirement to want both 208v and 
> 120v from single 3-phase 208v circuit, but I’d figured I’ll ask the list 
> to see how everyone else is coping with 208V environment when they have 
> a need for 120V access.

If it's 208 wye, then 120V is trivial.  Connect your convenience outlet 
between any hot leg and neutral.

Any modern KVM gear will handle 120 or 208 automatically so the need for 
a 120V outlet may not be as great as you think.  For carts with a NEMA 
5-15, consider stowing a long extension cord in the rack as most 
buildings will have convenience outlets on the wall for such temporary 
use.

--
Jay Hennigan - CCIE #7880 - Network Engineering - [email protected]
Impulse Internet Service  -  http://www.impulse.net/
Your local telephone and internet company - 805 884-6323 - WB6RDV
-- 
Eat sushi frequently. - Avi
[email protected] is the human contact address.
[email protected] is the list posting address.
See below URL for subscribe/unsubscribe and list options:
http://inet-access.net/mailman/listinfo/list