Re: R 3rd party lithium battery replacements safe & OK 2 use?
[email protected] (Ant) Thu, 3 Apr 2025 19:50:59 -0000 (UTC)
| Newsgroups | alt.comp.hardware |
|---|---|
| Organization | A noiseless patient Spider |
| Message-ID | <[email protected]> |
Paul <[email protected]> wrote: > On Wed, 4/2/2025 4:20 PM, Ant wrote: > > Are those third party lithium battery replacements (e.g., > > https://a.co/d/bjBzSf4) safe and good to use for APC UPSes? > "The operating current of 12V 10Ah battery is 10A, > and the maximum instantaneous current is 30A(5 seconds)." > That means the battery can put out 120W continuously. > Now, work out the max power output of the APC = 650W > You're running a 650W UPS using a 120W (continuous) battery. > That does not sound right, somehow :-) And do you really want > to leave four or five additional batteries sitting on your > night table ? I think not. > The UPS will float charge them constantly at 13.5V . > Lithium do not float charge (officially, you're not > supposed to do that). Proper lithium charging requires the > charger to stop... and not start charging again, until the battery > is discharged somewhat. The APC does not know you have connected > LFP -- it is not a mind reader. > LFP (LiFeP04) chemistry is specifically selected for this product, > due to its "tolerance of abuse". NMC could not be abused > like this. You can put current into LFP, even when it > does not want the current. LFP has lower power density and the ability > to be abused on its charge cycle. It also has a slightly > higher charge cycle count than laptop batteries do (if you treat > them right). These cells are not used in laptops or inside phones > (not enough runtime, lower power density). > I don't really know, how to gauge when one of these is failing. > Sure, it might fail the once-a-day impedance test (which > lasts for a second or two), but how beat to death would > this particular battery chemistry be, when it triggers the > "beep" thing ? APC UPS only beep once on an impedance failure. > You can tell when an APC SPS (Standby Power Supply) UPS is > failing, by the metal case temperature. An ice-cold APC SPS > is working properly. If the APC gets lukewarm to the touch, > that means your lead acid pack has shorted-out cells inside. > Time to replace, when the housing gets even a bit warm. > The SPS type does not dissipate power when in quiet mode, > which is why it can be cold like that. When it floats the > battery at 13.5V, hardly any current flows into a "healthy" battery. > Maybe 5-10mA. How much current flows into the LFP pack ??? > I don't know. And my livingroom seems a poor place for > pyrotechnical experiments. > ******* > The price of a kilowatt hour of battery has dropped a lot over time. > This battery is priced as if the price had never dropped. It's still > a thousand bucks. You can put eight of these in parallel, but the advert > says the battery is limited to 50A discharge current (instead of the > 100A by itself). With eight of those in parallel, you get 400A continuous. > You can put two of the batteries in series, making 24V @ 100A. But at that > price, you won't be doing that. And because it has a pushbutton control, > you won't be buying that (it likely means a BMS test circuit is being > used as a power control). Batteries have cells, but they have a BMS > (Battery Management System) circuit board on top which monitors the > cells and may attempt to "balance" the battery during charging. > https://batterybrands.com.au/products/pylontech-rv12100-12-8v-100ah-1280wh-4s4p-lifepo4-battery-soc-indicator-m8-terminals-max-2s-or-8p-ip20-rating > At the price of those batteries, you don't abuse those with a float charge. > You would use a proper Lithium charger that cuts off the charger when > the pack is full. It would not fit into your APC, but it would be > a bit closer to the correct capacity numbers. And it's $1000 so you > won't be buying that anyway. > The State of Charge (SoC) indicator on that pack, is four LEDs and a push button. > You press the switch, and if four LEDs light up, the battery is full. Take > your finger off the test button and the LEDs stop illumination. Some laptop > packs used to have a SoC like that on them. Four LEDs. > If I could find an authoritative source claiming "this was OK for X years", > I would tell you that. So far, I haven't seen a BatteryUniversity.com app note > on this. That's our source of non-pyrotechnical battery operation info :-) > I believe some domestic Japanese UPS are using Lithium. I haven't checked > lately, to see if anyone in North America has had the cheek to do that > (fire risk). No, you can't buy the Japanese one as it is the wrong voltage. > That helps prevent grey-market sales of such. When they are good and > ready to make a 115V one, they'll make one. > Since they are constantly working on new battery designs, I believe one > day, we will be shed of the 3-year-drop-dead Lead Acid ones and we will > get a quality design. But it's not ready quite yet. Solid state electrolyte Li > is one possible type. Expect abusive pricing on the batteries, as the > batteries will never match lead acid on price. People insist on selling > $100 per kWh batteries for $1000 per kWh. "Bad monkey bad". Thanks Paul. I was debating to get new APC Replacement Battery Cartridge (APCRBC124) battery replacements for my old 865 watts APC Back-UPSes: XS 1500 (model: BX1500G) and APC Back-UPS XS 1500 (model BX1500G). One of them show a blinking battery icon due to its old age. :( -- "Whatever you have learned or received or heard from me, or seen in me ? put it into practice. And the God of peace will be with you." --Philippians 4:9. Flow movie was beautiful with an odd ending. Note: A fixed width font (Courier, Monospace, etc.) is required to see this signature correctly. /\___/\ Ant(Dude) @ http://aqfl.net & http://antfarm.home.dhs.org. / /\ /\ \ Please nuke ANT if replying by e-mail. | |o o| | \ _ / ( )