Jay Hennigan <[email protected]>
| Newsgroups | gmane.org.operators.internet-access |
|---|---|
| Message-ID | <[email protected]> |
Blake Pfankuch wrote: > So we ran into an issue the other night that was power related, long > story short the mains to the datacenter had the wrong fuses. Anyone > ever run into Slow Blow Voltage limiting fuses? When they actually > trigger, the limit voltage passing through them to 50% until you reset > them by removing them and putting them back in. These were 100A fuses > on a 220 main. The way the room was wired, it allowed some stuff to > still function as it was 110, but the rest of the 220 stuff died out. > Can anyone think of a practical reason to put these on dedicated mains > to a small datacenter? I think you have something else going on. Such a device wouldn't be a fuse. It would have to be either a resistor that could dissipate half of the power (think large and with a huge heatsink) or a diode, triac, or some other type of thyristor. Not the type of thing one would normally find in a fuseholder. I would look for one phase opening up or possibly a floating neutral. Make sure all of the connections are tight. -- Jay Hennigan - CCIE #7880 - Network Engineering - [email protected] Impulse Internet Service - http://www.impulse.net/ Your local telephone and internet company - 805 884-6323 - WB6RDV _______________________________________________ "Eat sushi frequently". - Avi [email protected] is the human contact address. [email protected] is the list posting address. See below URL for subscribe/unsubscribe and list options: http://inet-access.net/mailman/listinfo/list