RE: slightly off topic
"Blake Pfankuch" <bpfankuch-iDUpQSA8o47qlBn2x/[email protected]>
| Newsgroups | gmane.org.operators.internet-access |
|---|---|
| Message-ID | <[email protected]> |
Checked that. They were all tight. All we did was reset the "fuse" and everything came back. This device, whatever you decide it is, didn't seem to drigger until we generated more than 100A of draw for about 5 minutes. All phases of the main were live, and I checked connections. Everything was tight. -----Original Message----- From: [email protected] [mailto:[email protected]] On Behalf Of Jay Hennigan Sent: Sunday, March 02, 2008 10:35 PM To: [email protected] Subject: Re: slightly off topic Blake Pfankuch wrote: > So we ran into an issue the other night that was power related, long > story short the mains to the datacenter had the wrong fuses. Anyone > ever run into Slow Blow Voltage limiting fuses? When they actually > trigger, the limit voltage passing through them to 50% until you reset > them by removing them and putting them back in. These were 100A fuses > on a 220 main. The way the room was wired, it allowed some stuff to > still function as it was 110, but the rest of the 220 stuff died out. > Can anyone think of a practical reason to put these on dedicated mains > to a small datacenter? I think you have something else going on. Such a device wouldn't be a fuse. It would have to be either a resistor that could dissipate half of the power (think large and with a huge heatsink) or a diode, triac, or some other type of thyristor. Not the type of thing one would normally find in a fuseholder. I would look for one phase opening up or possibly a floating neutral. Make sure all of the connections are tight. -- Jay Hennigan - CCIE #7880 - Network Engineering - [email protected] Impulse Internet Service - http://www.impulse.net/ Your local telephone and internet company - 805 884-6323 - WB6RDV _______________________________________________ "Eat sushi frequently". - Avi [email protected] is the human contact address. [email protected] is the list posting address. See below URL for subscribe/unsubscribe and list options: http://inet-access.net/mailman/listinfo/list _______________________________________________ "Eat sushi frequently". - Avi [email protected] is the human contact address. [email protected] is the list posting address. See below URL for subscribe/unsubscribe and list options: http://inet-access.net/mailman/listinfo/list